Commit 679d0b6f authored by Claes Sjofors's avatar Claes Sjofors

Remote rk512 ported from ELN

parent 3e599866
include $(pwre_dir_symbols)
-include $(pwre_kroot)/tools/bld/src/$(os_name)/$(hw_name)/$(type_name)_generic.mk
ifeq ($($(type_name)_generic_mk),)
-include $(pwre_kroot)/tools/bld/src/$(os_name)/$(type_name)_generic.mk
endif
ifeq ($($(type_name)_generic_mk),)
include $(pwre_kroot)/tools/bld/src/$(type_name)_generic.mk
endif
ifndef link_rule_mk
link_rule_mk := 1
link = $(ldxx) $(elinkflags) $(domap) -o $(export_exe) \
$(export_obj) $(objects) $(rt_msg_eobjs) \
$(pwre_conf_libdir) $(pwre_conf_libpwrremote) $(pwre_conf_libpwrrt) $(pwre_conf_lib)
endif
...@@ -61,6 +61,7 @@ ...@@ -61,6 +61,7 @@
* i skvgarna till exe-filerna * i skvgarna till exe-filerna
* 040422 C Jurstrand 4.0.0 * 040422 C Jurstrand 4.0.0
* 101209 R Karlsson Adderat std fr Websphere MQ * 101209 R Karlsson Adderat std fr Websphere MQ
* 111102 cs RK512 ported from ELN version.
* *
* Description: * Description:
* Start and control of transportprocesses for remote communication * Start and control of transportprocesses for remote communication
...@@ -329,6 +330,28 @@ static void AddTransports() ...@@ -329,6 +330,28 @@ static void AddTransports()
sts = gdh_GetNextObject (objid, &objid); sts = gdh_GetNextObject (objid, &objid);
} }
sts = gdh_GetClassList (pwr_cClass_RemnodeRK512, &objid);
while ( ODD(sts))
{
sts = gdh_ObjidToPointer(objid, &objref);
sprintf(tp[tpcount].path, "rs_remote_rk512");
tp[tpcount].id = 0;
tp[tpcount].disable = &((pwr_sClass_Remnode3964R *) objref)->Disable;
tp[tpcount].restart_limit = &((pwr_sClass_RemnodeRK512 *) objref)->RestartLimit;
tp[tpcount].restarts = &((pwr_sClass_RemnodeRK512 *) objref)->RestartCount;
((pwr_sClass_RemnodeRK512 *) objref)->RestartCount = 0;
tp[tpcount].objid = objid;
tp[tpcount].objref = objref;
tp[tpcount].classid = pwr_cClass_RemnodeRK512;
tp[tpcount].cpid = -1;
tp[tpcount].first = true;
remcfgp->RemNodeObjects[tpcount] = objid;
tpcount++;
sts = gdh_GetNextObject (objid, &objid);
}
return; return;
} }
......
!
! Proview Open Source Process Control.
! Copyright (C) 2005-2011 SSAB Oxelosund AB.
!
! This file is part of Proview.
!
! This program is free software; you can redistribute it and/or
! modify it under the terms of the GNU General Public License as
! published by the Free Software Foundation, either version 2 of
! the License, or (at your option) any later version.
!
! This program is distributed in the hope that it will be useful
! but WITHOUT ANY WARRANTY; without even the implied warranty of
! MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
! GNU General Public License for more details.
!
! You should have received a copy of the GNU General Public License
! along with Proview. If not, see <http://www.gnu.org/licenses/>
!
! Linking Proview statically or dynamically with other modules is
! making a combined work based on Proview. Thus, the terms and
! conditions of the GNU General Public License cover the whole
! combination.
!
! In addition, as a special exception, the copyright holders of
! Proview give you permission to, from the build function in the
! Proview Configurator, combine Proview with modules generated by the
! Proview PLC Editor to a PLC program, regardless of the license
! terms of these modules. You may copy and distribute the resulting
! combined work under the terms of your choice, provided that every
! copy of the combined work is accompanied by a complete copy of
! the source code of Proview (the version used to produce the
! combined work), being distributed under the terms of the GNU
! General Public License plus this exception.
!
! remote_c_remnoderk512.wb_load -- Defines the class RemnodeRK512.
!
SObject Remote:Class
!/**
! @Version 1.0
! @Group Servers,NodeConfiguration
! @Summary Configures communication to a remote system using Siemens RK512 on a serial line.
! Configures communication to a remote system using Siemens RK512 on a serial line..
!
! @b Object graph
! @image orm_remnoderk512_og.gif
!
! @b See also
! @classlink RemoteConfig pwrp_remoteconfig.html
! @classlink RemTrans ssab_remtrans.html
!*/
Object RemnodeRK512 $ClassDef 9
Body SysBody
Attr Editor = pwr_eEditor_AttrEd
Attr Method = pwr_eMethod_Standard
Attr PopEditor = 2
EndBody
Object RtBody $ObjBodyDef 1
Body SysBody
Attr StructName = "RemnodeRK512"
EndBody
!/**
! Optional description.
!*/
Object Description $Attribute 1
Body SysBody
Attr TypeRef = "pwrs:Type-$String80"
EndBody
EndObject
!/**
! Process priority for the transport process. For future use.
!*/
Object Prio $Attribute 2
Body SysBody
Attr TypeRef = "pwrs:Type-$Int32"
EndBody
EndObject
!/**
! Device name for the serial port, ex /dev/ttyS0.
! Dynamic change is not possible.
!*/
Object DevName $Attribute 3
Body SysBody
Attr TypeRef = "pwrs:Type-$String32"
EndBody
EndObject
!/**
! Baud rate for the serial port, ex 9600.
! Dynamic change is not possible.
!*/
Object Speed $Attribute 4
Body SysBody
Attr TypeRef = "pwrs:Type-$UInt32"
EndBody
EndObject
!/**
! Type of parity for the serial port.
! Dynamic change is not possible.
!*/
Object Parity $Attribute 5
Body SysBody
Attr TypeRef = "pwrs:Type-$Enum"
EndBody
EndObject
!/**
! Number of stop bits for the serial port.
! Dynamic change is not possible.
!*/
Object StopBits $Attribute 6
Body SysBody
Attr TypeRef = "pwrs:Type-$Enum"
EndBody
EndObject
!/**
! Number of data bits for the serial port.
! Dynamic change is not possible.
!*/
Object DataBits $Attribute 7
Body SysBody
Attr TypeRef = "pwrs:Type-$Enum"
EndBody
EndObject
!/**
! Timeout time in seconds between two characters used while reading data.
! Dynamic change is possible.
!*/
Object CharTimeout $Attribute 8
Body SysBody
Attr TypeRef = "pwrs:Type-$Float32"
EndBody
EndObject
!/**
! Timeout time in seconds used when waiting for DLE (acknowledge) in sending,
! and when waiting for data after sending DLE in receiving.
! Dynamic change is possible.
!*/
Object AckTimeout $Attribute 9
Body SysBody
Attr TypeRef = "pwrs:Type-$Float32"
EndBody
EndObject
!/**
! Attribute that indicates connection with the remote node.
! The link is considered down when we reach the link supervision timeout
! time without receiving any valid message.
! The link is considered up again when receiving a valid message.
!*/
Object LinkUp $Attribute 10
Body SysBody
Attr TypeRef = "pwrs:Type-$Boolean"
Attr Flags |= PWR_MASK_STATE
Attr Flags |= PWR_MASK_NOEDIT
Attr Flags |= PWR_MASK_INVISIBLE
EndBody
EndObject
!/**
! Time in seconds before the link is considered down.
! Dynamic change is possible
!*/
Object LinkTimeout $Attribute 11
Body SysBody
Attr TypeRef = "pwrs:Type-$Float32"
EndBody
EndObject
!/**
! When set, this attribute tells the remote handler not to start
! or restart the process that handles this remote node. If the transport process
! is running while the attribute is set it will terminate.
! Dynamic change is possible.
!*/
Object Disable $Attribute 12
Body SysBody
Attr TypeRef = "pwrs:Type-$Boolean"
EndBody
EndObject
!/**
! This attribute shows how many times the remote handler has restarted the
! transport process that handles this remnode.
! Dynamic change is possible and can be used in order to earn more restarts.
!*/
Object RestartCount $Attribute 13
Body SysBody
Attr TypeRef = "pwrs:Type-$UInt32"
Attr Flags |= PWR_MASK_STATE
Attr Flags |= PWR_MASK_NOEDIT
Attr Flags |= PWR_MASK_INVISIBLE
EndBody
EndObject
!/**
! The restart limit tells the remote handler how many times the transport process
! that handle this remnode can be restarted.
! Dynamic change is possible and can be used in order to earn more restarts.
!*/
Object RestartLimit $Attribute 14
Body SysBody
Attr TypeRef = "pwrs:Type-$UInt32"
EndBody
EndObject
!/**
! The restart time is set by the transport process at startup and therefore
! shows the latest (re)starttime.
!*/
Object RestartTime $Attribute 15
Body SysBody
Attr TypeRef = "pwrs:Type-$Time"
Attr Flags |= PWR_MASK_STATE
Attr Flags |= PWR_MASK_NOEDIT
Attr Flags |= PWR_MASK_INVISIBLE
EndBody
EndObject
!/**
! Scantime in seconds for outgoing RemTrans objects.
! Dynamic change is possible.
!*/
Object ScanTime $Attribute 16
Body SysBody
Attr TypeRef = "pwrs:Type-$Float32"
EndBody
EndObject
!/**
! Error counter.
!*/
Object ErrCount $Attribute 17
Body SysBody
Attr TypeRef = "pwrs:Type-$UInt32"
Attr Flags |= PWR_MASK_STATE
Attr Flags |= PWR_MASK_NOEDIT
Attr Flags |= PWR_MASK_INVISIBLE
EndBody
EndObject
!/**
! Type of remnode. Used in the RemoteConfig classgraph.
!*/
Object Id $Attribute 18
Body SysBody
Attr TypeRef = "pwrs:Type-$String8"
Attr Flags |= PWR_MASK_INVISIBLE
EndBody
EndObject
!/**
! Contains the objid for the RemTrans objects for this remnode.
! The objid's are inserted by the remote process.
!*/
Object RemTransObjects $Attribute 19
Body SysBody
Attr TypeRef = "pwrs:Type-$Objid"
Attr Flags |= PWR_MASK_STATE
Attr Flags |= PWR_MASK_INVISIBLE
Attr Flags |= PWR_MASK_ARRAY
Attr Elements = 25
EndBody
EndObject
EndObject
Object Template RemnodeRK512
Body RtBody
Attr Prio = 15
Attr DevName = "/dev/ttyS0"
Attr Speed = 9600
Attr Parity = 2
Attr StopBits = 1
Attr DataBits = 8
Attr CharTimeout = 0.22
Attr AckTimeout = 2.0
Attr LinkUp = 0
Attr LinkTimeout = 10.0
Attr Disable = 0
Attr RestartCount = 0
Attr RestartLimit = 100
Attr ScanTime = 0.1
Attr Id = "rk512"
EndBody
EndObject